2 Channel analogue module with channel to channel isolation. The Module has 200 Mhz processor and support Hot Swap, Fail safe, Redundancy.

The Brodersen LB2 modules can be used with the RTU32N and RTU32M series products. The I/O modules are in two parts, a bottom part containing the backplane bus, and a top part containing the I/O board and logic. All LB2 I/O modules are hot pluggable and equipped with a 200 MHz processor to handle filtering, de-bouncing and logic processing of I/O.

Module firmware updates are managed by the RTU using Brodersen Worksuite. Use only genuine Brodersen bus cables for connection to Brodersen RTUs and extension of I/O module blocks. The LB2 connection cables are made to handle the power and shielding requirements of the LB2 bus communications. The maximum overall length of complete system is 30m. Each I/O module & Power supply module is calculated as 2cm. The cables are as their length indicates, e.g. UCC-610/100 cable is 100 cm. The maximum number of I/O modules on one LB2 Bus is 60

2 channels sourced configurable analog outputs.

Output ranges:

  • Current mode:
  • 0 to 20mA, 4mA to 20mA.

Output load for voltage mode:

  • Max load current:             10mA
  • Short circuit current:        20mA (typ.)

Output load for voltage mode:

  • Max load impedance:       1KΩ
  • Open circuit detection:    Yes

Resolution:                             16 bit

Accuracy (at 25°C):                ±0.1%

Nonlinearity:                         ± 0.02%

Temperature drift:                ± 25ppm/°C

Isolation:

  • Output to digital:               At least 1KV
  • Channel to channel:          At least 1KV

Ambient temperature range:

  • -40°C to +70°C

 