8 Analog input Module-AI08A
Quick Information
8 channel analogue module with channel to channel isolation. Each channel can be configured with. Range, Delta change, Filter, Scale Min, Scale Max. Super fast with 200 Mhz processor and 16 Bit AD

The Brodersen LB2 modules can be used with the RTU32N and RTU32M series products. The I/O modules are in two parts, a bottom part containing the backplane bus, and a top part containing the I/O board and logic. All LB2 I/O modules are hot pluggable and equipped with a 200 MHz processor to handle filtering, de-bouncing, and logic processing of I/O. Module firmware updates are managed by the RTU using Brodersen Worksuite. Use only genuine Brodersen bus cables for connection to Brodersen RTUs and extension of I/O module blocks.
The LB2 connection cables are made to handle the power and shielding requirements of the LB2 bus communications. The maximum overall length of the complete system is 30m. Each I/O module & Power supply module is calculated as 2cm. The cables are as their length indicates, e.g. UCC-610/100 cable is 100 cm. The maximum number of I/O modules on one LB2 Bus is 60
Number of input channels: 8 differential channels
Analog input type: Voltage / Current
Input ranges: Each channel can be configured individual
- Voltage mode: 0-10V, 0-5V, ±5V, ±10V
- Current mode: 0-20mA, ±20mA, 4-20mA
Effective resolution: 16 bit
Update time: 30ms (for all 8 channels)
Accuracy (at 25°C): ±0.1%
Temperature drift: ± 25ppm/°C
Power-freq. noise rejection: 50Hz
Digital low-pass filter: User selectable
Power supply (from backplane bus):
- Supply voltage: 12 VDC ±20%
- Power consumption: 80mA (typ.) @ 12V
Input impedance:
- Voltage mode: More than 1MΩ
- Current mode: 250 Ohm ±0.1%
Isolation:
- Input to digital: At least 1KV
- Channel to channel: At least 350V
Absolute maximum ratings:
- Voltage: ±40V DC
- Current: ±40mA
Temperature range
- Ambient: -25°C to +75°C
- Storage: -40°C to +85°C